China Testing Instruments Manufacturer,Whatsapp/Wechat:+8619928310111  Email: 2601804145@qq.com

Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter
Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter
Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter
Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter
Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter
Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter

Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter

2024-07-22 15:48:28  

Xtester-TG9 Duct Air Quality CO2 TVOC Transmitter

  • Main Feature :
  • Serial No. : Lisa0644
Contact Us For QuotationEmail:  464560351@qq.comWhatsapp&Wechat:+8618620373879

Musktool-TG9 Duct Air Quality CO2 TVOC Transmitter

oerview

Real time detect carbon dioxide plus tvoc (mix gases) of the air duct, also optional temperature and relative humidity. A smart sensor probe with the water-proof and porous film can be easily installed into any air duct. LCD display is available if required. It provides one, two or three 0-10V / 4-20mA linear outputs. The end user can adjust CO2 range which correspond with the analog outputs via Modbus RS485, also can preset the inverse proportion liner outputs for some different applications.

FEATURES

Real time carbon dioxide detection in air duct
High accuracy temperature and relative humidity
with extendable air probe into air duct
Equiped With the water-proof and porous film around the sensor probe
Up to 3 analog linear outputs for 3 measurements
Modbus RS485 interface for 4 measurements
With or without LCD display
CE-approval

TECHNICAL SPECIFICATIONS

Monitoring parameters

CO2

Temperature

Relative humidity
Sensing elementNon-Dispersive Infrared Detector (NDIR)Digital combined temperature and humidity sensor
Measuring range

0~2000ppm(default) 0~5000ppm

(selectable in the order)

0℃~50℃(32℉~122℉) (default)0~100%RH
Display Resolution

1ppm

0.1℃

0.1%RH
Accuracy@25℃(77℉)±60ppm + 3% of reading

±0.5℃ (0℃~50℃)

±3%RH (20%-80%RH)

Life time

15 years (normal)

10 years

Calibration cycleABC Logic Self Calibration

——

——

Response Time<2 minutes for 90% change<10 seconds to reach 63%
Warm up time2 hours (first time)2 minutes (operation)

Electrical Characteristics

Power supply24VAC/VDC
Consumption3.5 W max. ; 2.5 W avg.

Outputs

Two or three analog outputs0~10VDC(default) or 4~20mA (selectable by jumpers) 0~5VDC (selected at place the order)
Modbus RS485 interface (optional)RS-485 with Modbus protocol, 19200bps rate, 15KV antistatic protection, independent base address

Conditions of Using and Installation

Operation conditions0~50℃(32~122℉); 0~95%RH, non condensing
Storage conditions0~50℃(32~122℉)/ 5~80%RH

Weight

320g
InstallationFixed on the air duct with 100mm installation hole size
 IP class of the housingIP50 for no LCD IP40 for with LCD
StandardCE-Approval




Telephone
Email
Map
QQ Chat