Musktool- JYZ-HW Remote Overhead Line Fault Indicator
Product Overview
The JYZ-HW is designed for 5–38kV overhead line distribution networks (customizable up to 44kV, 69kV, or 110kV) to detect and indicate short-circuit and earth faults. It transmits fault signals via ultra-bright LEDs and uploads fault data to SCADA systems using 2.5G/3G/4G networks. The device supports live-line installation and bidirectional wireless parameter adjustment. |
Technical Specifications
Parameter | Specification |
Voltage Range | 5–38kV (customizable to 44kV, 69kV, 110kV). |
Short-circuit Trip Current | 50–1200A adjustable (1A step, default 150A). |
Earth-fault Voltage Drop | Adjustable (1% step, default 30%). |
Earth-fault Response Delay | Adjustable (1s step, default 30s). |
Reset Methods | Manual (magnet), remote (SCADA), time-based (24h default, max 48h), auto-repower (30s default). |
Protection Class | IP68 |
Operating Temperature | -40℃ to +70℃ |
Power Supply | 3.6V/9Ah lithium battery (replaceable), 10-year lifespan. |
Dimensions | Diameter: 93mm, Height: 170mm. |
Weight | Indicator: ~600g; DCU: ~3.6kg. |
Accuracy | 0–300A: ±3A; 300–800A: ±1%. |
Cable Diameter Range | 6–42mm |
Blinking Frequency | 10/min (adjustable). |
Max Load/Fault Current | 1200A |
Current Withstand | 31.5kA for 4s. |
Communication | Indicators to DCU: 433MHz private protocol. DCU to SCADA: 2.5G/3G/4G (IEC101/104, DNP3.0, Modbus). |
Ordering Information
Item | Options |
Type | Local (3 indicators) / Remote (3 indicators + 1 DCU). |
Voltage Level | Specify kV and frequency (Hz). |
SIM Card | 1 or 2 slots. |
Accessories | Solar panel, battery, housing, DC adapter. |