Contact Us For Quotation | Email: 464560351@qq.com | Whatsapp&Wechat:+8618620373879 |
Musktool-Fluke 369 FC Leakage Current Clamp Meter,WIRELESS LEAKAGE CURRENT CLAMP METER 61MM JAW,PINZA FLUKE MODELO:369 FC|PINZA PARA CORRIENTE DE FUGA|WIRELESS LEAKAGE CURRENT CLAMP METER, 61MM JAW|UNIDADES|FLUKE-369 FC
Key Features
|
Overview
Product overview: Fluke 369 FC Leakage Current Clamp MeterReduce downtime – Find leakage currents without taking equipment offline. The Fluke 369 FC true-rms leakage current clamp meter helps users detect, document, record and compare leakage current readings over time as a means of preventing unplanned downtime, and identifying intermittent GFCI and RCD trips, all without taking equipment off line. The Fluke 369 FC has an oversize 61 mm jaw for work with extra-large conductors. The clamp’s jaw is fully shielded to accurately capture very small leakage signals, and to minimize external electromagnetic interference. The 369 FC also offers wireless data connectivity via Fluke Connect. As part of Fluke Connect — the industry’s largest system of software and more than 40 wireless test tools — the 369 FC allows you to track changes in leakage current over time, helping to identify potential problems before they turn into major failures |
Specifications: Fluke 369 FC Leakage Current Clamp Meter
Electrical Specifications | ||
Measurement function | Alternating current | |
AC ampere range | 3 mA, 30 mA, 300 mA, 3 A, 30 A, 60 A | |
Range selection | mA / A: manual selection 3 mA / 30 mA / 300 mA: automatic selection 3 A / 30 A / 60 A: automatic selection | |
Range / Resolution | 3 mA¹ / 0.001 mA | |
30 mA / 0.01 mA | ||
300 mA / 0.1 mA | ||
3 A / 0.001 A | ||
30 A / 0.01 A | ||
60 A / 0.1 A | ||
Accuracy – filter activated (40 to 70 Hz), filter off (40 to 1 kHz)² | 3 mA – 30 A 60 A | 1% + 5 digits 2% + 5 digits |
Frequency | 40 Hz to 1 kHz | |
Crest Factor | 3 | |
After calibration accuracy is valid for one year. Accuracy is expressed as ± (% of reading + digits). Reference conditions 23 ±5 °C and a maximum relative humidity of 80%. ¹The minimum value is 10 μA rms. ²Outside of the TC / °C 18 °C to 28 °C, 0.02 + 1 | ||
Physical | ||
Display (LCD) | Digital readout: 3300 count | |
Display refresh rate | 4 times / sec | |
Maximum conductor diameter | 61 mm | |
Dimensions | 257 x 116 x 46 mm | |
Weight | 600 g | |
Battery | 2 AA, IEC LR6, NEDA 15A, alkaline | |
Battery life | Expected battery life, without using backlight and spotlight, is more than 150 hours | |
Automatic shut-down | Meter automatically shuts down after 15 minutes of inactivity | |
Safety and Environmental Specifications | ||
General safety | IEC 61010-1: Pollution Degree 2 | |
Measurement safety | IEC 61010-2-032: CAT III 600 V / CAT IV 300 V | |
Operating temperature | -10 °C to +50 °C | |
Storage temperature | -40 °C to +60 °C | |
Operating humidity | Non-condensing (<10 °C) | |
90% relative humidity (10 °C to 30 °C) | ||
75% relative humidity (30 °C to 40 °C) | ||
45% relative humidity (40 °C to 50 °C) | ||
Protection class | IEC 60529: IP30 (jaw closed) | |
Operating altitude | 2000 m | |
Storage altitude | 12000 m | |
Current sensor action category | IEC 61557-13: Class 1, ≤100 A / m | |
Electromagnetic compatibility (EMC) | ||
International | ||
IEC 61326-1 | Industrial Electromagnetic Environment | |
CISPR 11 | Group 1 Class B | |
Group 1 | Generated inside the equipment and / or use radio frequency energy associated with conducting the energy for the device's own internal functions is essential. | |
Class B | Equipment for home appliances and residential buildings directly connected to a low voltage power supply network equipment. When this device is connected to a test object, it may exceed the emission levels produced by CISPR 11 requirements. Korea (KCC): Class A Equipment (Industrial Broadcasting & Communication Equipment) | |
Class A | This product meets the requirements of industrial electromagnetic equipment, vendors or users should be aware of this. This device is intended for use in a commercial environment, instead of the home environment. USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103. |