Product Overview

The F-FTU200L is a critical component in distribution grid automation, designed to enable Fault Detection, Isolation, and Restoration (FDIR). It reduces outage time, improves power supply reliability, and integrates seamlessly with SCADA systems to achieve "four-remote" functions (remote signaling, telemetry, control, and regulation). Compatible with IEC/ANSI standards, it supports Load Break Switches (LBS) and offers versatile automation solutions for overhead lines.


Technical Specifications

Function

Description

Current Protection

ANSI 50/51 (3-phase over-current), 50N/51N (earth-fault), 64N (sensitive earth-fault), 46 (negative-sequence), 68 (inrush restraint).

Voltage Protection

ANSI 59 (over-voltage), 27 (under-voltage), 47 (negative-sequence), Loss of Phase Detection.

Other Protections

Phase Reverse Detection, 5 Setting Groups.

Measurement

Parameter

Accuracy

3-Phase Current

±0.5% (0.1–1.2 In)

Residual Current

±0.5% (measured), ±1.0% (calculated)

6-Phase Voltage

±0.5% (0.05–2.00 Un)

Active/Reactive Power

±1.0%

Frequency

±0.02 Hz (0.8–1.2 Fn)

Harmonics (THD)

Up to 11th order for voltage/current.

Demand Time

1/5/15/30/60/180 minutes.

Communication

Interface

Details

Front Port

1×RJ45 (debugging).

Rear Ports

1×RS232, 1×RS485/232, 1×RJ45 (SCADA).

Protocols

IEC 60870-5-101/104, DNP3.0 (Level II), MODBUS.

Hardware

Component

Specifications

Power Supply

100–240V AC (from voltage transformer).

Current Input

1A/5A secondary (current transformer).

Voltage Input

0–4V secondary (voltage sensor).

Binary I/O

8 inputs (expandable to 16), 4 outputs (expandable to 8).

Analog Input

2×4–20mA channels.

HMI

10×20 character LCD, 16 programmable LEDs, 10 programmable buttons.

Battery

2×12V/12AH.

General

Parameter

Details

Control Mode

Local/Remote.

Alarms

AC/DC failure, battery low voltage.

Enclosure

304 stainless steel, IP55 protection.

Dimensions

675mm × 420mm × 330mm (L×W×H).

Weight

~2.03 kg (including accessories).